Apcupsd EVENTS

When apcupsd detects anomalies from your UPS device, it will make some decisions that usually result in one or more calls to the script located in /etc/apcupsd/apccontrol. The apccontrol file is a shell script that acts on the first argument that apcupsd passes to it. These actions are set up by default to sane behaviour for all possible situations apcupsd is likely to detect from the UPS. Nevertheless you can change the apccontrol behaviour for every single action. To do so create a file with the same name as the action, which is passed as a command line argument. Put your script in the /etc/apcupsd directory.

These events are sent to the system log, optionally sent to the temporary events file (/etc/apcupsd/apcupsd.events), and they also generate a call to /etc/apcupsd/apccontrol which in turn will call any scripts you have placed in the /etc/apcupsd directory.

Normally, /etc/apcupsd/acpcontrol is called only by apcupsd. Consequently, you should not invoke it directly. However, it is important to understand how it functions, and in some cases, you may want to change the messages that it prints using wall. We recommend that you do so by writing your own script to be invoked by apccontrol rather than by modifying apccontrol directly. This makes it easier for you to upgrade to the next version of apcupsd

In other case, you may want to write your own shell scripts that will be invoked by apccontrol. For example, when a power fail occurs, you may want to send an email message to root. At present the arguments that apccontrol recognizes are:

How apcupsd calls apccontrol

When apcupsd detects an event, it calls the apccontrol script with four arguments as:

apccontrol <event> <ups-name> <connected> <powered>

where:
event
is the event that occurred and it may be any one of the values described in the next section.
ups-name
is the name of the UPS as specified in the configuration file (not the name in the EEPROM). For version 3.8.2, this is always set to Default
connected
is 1 if apcupsd is connected to the UPS via a serial port (or a USB port). In most configurations, this will be the case. In the case of a Slave machine where apcupsd is not directly connected to the UPS, this value will be 0.
powered
is 1 if apcupsd is powered by the UPS and 0 if not. In version 3.8.2, this value is always 1.

apccontrol Command Line Options

apccontrol accepts the following command line options:

annoyme
Does a   printf "Power problems please logoff." | wall    then exits.
changeme
Does a    printf "Emergency! UPS batteries have failed\nChange them NOW" | wall    then exits.
commfailure
Does a   printf "Warning serial port communications with UPS lost." | wall    then exits.
commok
Does a   printf "Serial communciations with UPS restored." | wall   then exits.
doreboot
Does a reboot of the system by calling    shutdown -r now
doshutdown
Does a shutdown of the system by calling   shutdown -h now
emergency
Does an emergency shutdown of the system by calling   shutdown -h now
failing
Does a  printf "UPS battery power exhaused. Doing shutdown.\n" | wall   then exits.
loadlimit
Does a    printf "UPS battery discharge limit reached. Doing shutdown.\n" | wall    then exits. After completeting this event, apcupsd will immediately initiate a    doshutdown event.
mainsback
Attempts to cancel the shutdown with a    shutdown -c
onbattery
Does a   printf "Power failure. Running on UPS batteries." | wall   then exits.
powerout
Does a   printf "Warning power loss detected." | wall   then exits.
remotedown
Does a    shutdown -h now
restartme
Terminates the currently running apcupsd and then restarts it.
runlimit
Does a   printf "UPS battery runtime percent reached. Doing shutdown.\n" | wall    then exits. After completeting this event, apcupsd will immediately initiate a doshutdown event.
timeout
Does a   printf "UPS battery runtime limit exceded. Doing shutdown.\n" | wall    then exits. After completeting this event, apcupsd will immediately initiate a doshutdown event.
startselftest
This is called when apcupsd detects that the UPS is doing a self test. No action is taken.
endselftest
This is called when apcupsd determines that a self test has been completed. No action is taken.

To write your own routine for the powerout action, you create shell script named powerout and put it in the lib directory (normally /etc/apcupsd). When the powerout action is invoked by apcupsd, apccontrol will first give control to your script. If you want apccontrol to continue with the default action, simply exit your script with an exit status of zero. If you do not want apccontrol to continue with the default action, your script should exit with the special exit code of 99. However, in this case, please be aware that you must ensure proper shutdown of your machine if necessary.

Some sample scripts (onbattery and mainsback) that email power failure messages can be found in the examples directory of the source code.